Unit Had No Freon

Unit had no Freon. Added nitrogen and started to leak check. Found three leaks on condensing unit. Welded all three and pulled a good vacuum and made sure it held. Added 20 pounds of 404a and also replaced filter drier. Verified temp drop and proper operation on 2/5/24 in Arlington Texas. Near W Pioneer Pkwy […]

Hoshizaki Ice Machine Turning Off on High Pressure

Hoshizaki ice machine turning off on high pressure the condenser motor is no good. Removed and replaced condenser motor and verified proper operation on 1/29/24 in Arlington Texas. Near E Lamar Blvd Arlington, Texas 76006 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Substation Had a Dirty Condenser Coil

Substation had a dirty condenser coil. Wet it down and the blew it with nitrogen pressure to clean it out on 1/4/24 in Bedford Texas. Near Bedford Rd Bedford, Texas 76021 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Repaired Leak on Liquid Line Caused by Rubbing

Repaired Leak on Liquid Line Caused by Rubbing as previous installer looped line set three times and then into penetration and the rubbing of line set against each other slowly ate away at the copper and produced a leak on 1/3/24 in Mansfield Texas. Near FM157 Mansfield, Texas 76063 Check out the Areas We Serve […]

Clock is Pretty Hard to Move Freely

Clock is pretty hard to move freely. I removed and replaced defrost timer on 12/18/23 in Mansfield Texas. Near FM157 Mansfield, Texas 76063 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Unit Had a Major Leak When I Arrived

Unit had a major leak when I arrived. I could still hear it blowing when I got there. Didn’t take me long to find. Was able to solder the leak and checked around the area for other leaks. Pulled vacuum and charged system with 404a instead of 407a on 12/7/23 in Arlington Texas. Near E […]

Plug Harness Connection Came Loose

Plug harness connection came loose. I fixed the wiring and then verified that everything was in good working order on 12/1/23 in Arlington Texas. Near E Park Row Dr. Arlington, Texas 76010 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Pumped Down System and Replace Suction and Liquid Driers

Pumped down system and replace suction and liquid driers. Also replace oil sensor on 11/14/23 in Fort Worth Texas. Near Trinity Blvd Fort Worth, Texas 76155 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Leak Checked with Bubbles

Leak checked with bubbles and found micro leak at suction line fitting going to compressor. Pumped down unit and spot welded with brass flux core solder. Retest leak and good now. Rinsed off oil with hose and rinsed out condenser as well. Reassemble unit and place back into service on 11/13/23 in Arlington Texas. Near […]

Crane Arrived to Remove Old Compressor

Crane arrived to remove old compressor and set the new down in its place and reconnected the piping and started the provides of putting everything back together. I capped off all of the openings on the old compressor and took it back to claim the warranty on 10/28/2023 in Fort Worth Texas. Near Trinity Boulevard […]