Menu Blood Plasma Freezers Chiller Repairs Energy Management Freezers Glycol Chiller Hot Side Repair HVAC Installs HVAC Repairs Ice Machine Ice Machine Rentals Maintenance Swift Sensors Truck Refrigeration Ice Merchandiser Walk-In Cooler Wine Coolers Hospital Refrigerator Service Hospital Refrigerator Service, call was for a Lab refrigerator. I tested all electrical components, Amped out compressor 4.3 […]

Unit was Frozen Over

Unit was frozen over. After I thawed unit out found evaporator was dirty and clogged full of debris. I cleaned evaporator coil started it up verified charge and watch box go down from 50 to 40. all ops normal at this time on 9/5/24 in Fort Worth Texas. Near N Collins St Arlington, TX 76011 […]

Capacitor Blown and Burnt Wiring

Capacitor blown and burnt wiring. Made wiring repairs and replaced capacitor. started unit up verified operation all ops normal at this time on 8/23/24 in Fort Worth Texas. Near Bryant Irvin Rd Fort Worth, TX 76132 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Evaporator Motor Sluggish

Evaporator motor sluggish. Removed and installed new evaporator fan motor. Cold case getting to temp now on 8/21/24 in Fort Worth Texas. Near Tracewood Way Fort Worth, TX 76244 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Kitchen AC Had Hole in the Evaporator

Kitchen AC had hole in the evaporator. Welded hole and then began to pull vacuum. after reaching 450 microns, charged unit with 14lbs of r410, started unit up verified operation on 8/20/24 in Fort Worth Texas. Near N Beach St Fort Worth, TX 76137 Check out the Areas We Serve and jobs we are doing […]

AC Not Cooling

AC not cooling. Found low voltage wiring for second stage cooling disconnected, reconnected wiring unit cooling on 8/17/24 in Fort Worth Texas. Near N Beach St Fort Worth, TX 76137 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Leak Check and Repair

Leak check and repair. Found leak located on copper liquid line at compressor port. Brazed leak and removed old filter drier. Pressure tested welds with nitrogen. Pull vacuum to under 500 microns on 8/16/24in Fort Worth Texas. Near Bryant Irvin Rd Fort Worth, TX 76132 Check out the Areas We Serve and jobs we are […]

Contactors Short Cycling

Contactors short cycling, after further investigation found contactors for both stages were jumped at the thermostat board. After removing jumper from contactors started both units up and both now stayed on, all ops normal at this time on 8/11/24 in Fort Worth Texas. Near N Beach St Fort Worth, TX 76137 Check out the Areas […]

Found Compressor Pin Blown

Found compressor pin blown which caused unit to leak refrigerant. Replaced compressor and did start up. Confirmed operation all normal at this time on 7/30/24 in Fort Worth Texas. Near S Main St Fort Worth, TX 76104 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.arlington.prorefrigerationone.com/areas-we-serve/ [spacer]

Installed a Return Air on Package Unit

Installed a return air on package unit that was sitting on the roof to help the negative pressure in the building. We tested the doors and ran an unofficial balance test. The building is much more comfortable now on5/30/24 in Arlington Texas. Near S Collins St Arlington, TX 76018 Check out the Areas We Serve […]